Technical specifications

Technical dataMICROMASTER 430
Mains voltage and power ranges380 V to 480 V 3 AC  ±10 %7.5 kW to 250 kW (variable torque)
Power frequency47 Hz to 63 Hz
Output frequencyfor inverter 7.5 kW to 90 kW0 … 650 Hz, (limitation to 550 Hz in production to comply with legal requirements) 1)
for inverter 110 kW to 250 kW0 Hz to 267 Hz
Power factor≥ 0.95
Inverter efficiency

 

for inverter 7.5 kW to 90 kW96 % to 97 %
for inverter 110 kW to 250 kW97 % to 98 %
Overload capability

 

 

for inverter 7.5 kW to 90 kWOverload current 1.4 x rated output current (i.e. 140 % overload capability) for 3 s and 1.1 x rated output current (i.e. 110 % overload capability) for 60 s, cycle time 300 s
for inverter 110 kW to 250 kWOverload current 1.5 x rated output current (i.e. 150 % overload capability) for 1 s and 1.1 x rated output current (i.e. 110 % overload capability) for 60 s, cycle time 300 s
Inrush currentless than rated input current
Control methodlinear V/f characteristic; quadratic V/f characteristic; multipoint characteristic (programmable V/f characteristic); flux current control (FCC); energy saving mode
Pulse frequencyfor inverter 7.5 kW to 90 kW4 kHz (standard)
2 kHz to 16 kHz (in 2-kHz-steps)
for inverter 110 kW to 250 kW2 kHz (standard)
2 kHz to 4 kHz (in 2-kHz-steps)
Fixed frequencies15, programmable
Skip frequency ranges4, programmable
Setpoint resolution0.01 Hz digital
0.01 Hz serial
10 bit analog
Digital inputs6 fully programmable isolated digital inputs; switchable PNP/NPN
Analog inputs2 programmable analog inputs

  • 0 V to 10 V, 0 mA to 20 mA and –10 V to +10 V (AIN1)
  • 0 V to 10 V and 0 mA to 20 mA (AIN2)
  • both can be used as 7th/8th digital input
Relay outputs3, programmable
30 V DC/5 A (resistive load),
250 V AC/2 A (inductive load)
Analog outputs2, programmable (0/4 mA to 20 mA)
Serial interfacesRS-485, option RS-232
Motor cable lengthfor inverter 7.5 kW to 90 kWWithout output chokemax. 50 m (shielded)
max. 100 m (unshielded)
With output chokeSee variant dependent options
for inverter 110 kW to 250 kWWithout output chokemax. 200 m (shielded)
max. 300 m (unshielded)
With output chokeSee variant dependent options
Electromagnetic compatibility

 

 

 

for inverter 7.5 kW to 90 kWInverter with internal filter Class A available
for inverter without filter7.5 kW to 15 kWEMC filter Class B to EN 55 011 available as an option
18.5 kW to 90 kWEMC filter Class B from Schaffner available as an option
110 kW to 250 kWEMC filter Class A available as an option
BrakingDC braking, compound braking
Degree of protectionIP20
Operating temperature range

 

for inverter 7.5 kW to 90 kW-10 °C to +40 °C (+14 °F to +104 °F)
for inverter 110 kW to 250 kW0 °C to +40 °C (+32 °F to +104 °F)
Storage temperature-40 °C to +70 °C (-40 °F to +158 °F)
Relative humidity95 % (non-condensing)
Installation altitude

 

for inverter 7.5 kW to 90 kWup to 1000 m above sea level without derating
for inverter 110 kW to 250 kWup to 2000 m above sea level without derating
Standard SCCR
(Short Circuit Current Rating) 2)
FSC: 100 kA
FSD, FSE, FSF, FSFX, FSGX: 65 kA
Protection features forundervoltage, overvoltage, overload, earth faults, short-circuits, stall prevention, locked motor protection, motor overtemperature, inverter overtemperature, parameter change protection
Conformity with standardsfor inverter 7.5 kW to 90 kW UL, cUL, CE, c-tick
for inverter 110 kW to 250 kWUL available soon, cUL available soon, CE
CE markingConformity with low-voltage directive 73/23/EEC
Cooling-air volumetric flow required, dimensions and weights (without options)

 

Frame size (FS)Cooling-air volumetric flow required (l/s)/(CFM)H x W x D (mm)Weight, approx. (kg)
C54.9/116.3245 x 185 x 1955.7
D2 x 54.9/2 x 116.3520 x 275 x 24517
E2 x 54.9/2 x 116.3650 x 275 x 24522
F without filter150/317.79850 x 350 x 32056
F with filter150/317.791150 x 350 x 32075
FX225/478.131400 x 326 x 356116
GX440/9351533 x 326 x 545174