MICROMASTER 430 Inverter 30KW With Bilt-in Class a Filter3AC 380-480V 6SE6430-2AD33-0DA0

6SE6430-2AD33-0DA0 MICROMASTER 430 WITH BUILT-IN CLASS A FILTER 3AC 380-480 V +10/-10% 47-63 HZ SQUARED TORQUE POWER 30 KW OVERLOAD 110% 60 S, 140% 3 S

Sharing good things

Description

MICROMASTER 430 WITH BUILT-IN CLASS A FILTER 3AC 380-480 V +10/-10% 47-63 HZ SQUARED TORQUE POWER 30 KW OVERLOAD 110% 60 S, 140% 3 S 520 X 275 X 245 (H X W X D) PROTECTION IP20 AMBIENT TEMP. -10 TO +40 DEG. C WITHOUT AOP/BOP 6SE6430-2AD33-0DA0_datasheet_en

Technical specifications

Technical data MICROMASTER 430
Mains voltage and power ranges 380 V to 480 V 3 AC  ±10 % 7.5 kW to 250 kW (variable torque)
Power frequency 47 Hz to 63 Hz
Output frequency for inverter 7.5 kW to 90 kW 0 … 650 Hz, (limitation to 550 Hz in production to comply with legal requirements) 1)
for inverter 110 kW to 250 kW 0 Hz to 267 Hz
Power factor ≥ 0.95
Inverter efficiency

 

for inverter 7.5 kW to 90 kW 96 % to 97 %
for inverter 110 kW to 250 kW 97 % to 98 %
Overload capability

 

 

for inverter 7.5 kW to 90 kW Overload current 1.4 x rated output current (i.e. 140 % overload capability) for 3 s and 1.1 x rated output current (i.e. 110 % overload capability) for 60 s, cycle time 300 s
for inverter 110 kW to 250 kW Overload current 1.5 x rated output current (i.e. 150 % overload capability) for 1 s and 1.1 x rated output current (i.e. 110 % overload capability) for 60 s, cycle time 300 s
Inrush current less than rated input current
Control method linear V/f characteristic; quadratic V/f characteristic; multipoint characteristic (programmable V/f characteristic); flux current control (FCC); energy saving mode
Pulse frequency for inverter 7.5 kW to 90 kW 4 kHz (standard)
2 kHz to 16 kHz (in 2-kHz-steps)
for inverter 110 kW to 250 kW 2 kHz (standard)
2 kHz to 4 kHz (in 2-kHz-steps)
Fixed frequencies 15, programmable
Skip frequency ranges 4, programmable
Setpoint resolution 0.01 Hz digital
0.01 Hz serial
10 bit analog
Digital inputs 6 fully programmable isolated digital inputs; switchable PNP/NPN
Analog inputs 2 programmable analog inputs

  • 0 V to 10 V, 0 mA to 20 mA and –10 V to +10 V (AIN1)
  • 0 V to 10 V and 0 mA to 20 mA (AIN2)
  • both can be used as 7th/8th digital input
Relay outputs 3, programmable
30 V DC/5 A (resistive load),
250 V AC/2 A (inductive load)
Analog outputs 2, programmable (0/4 mA to 20 mA)
Serial interfaces RS-485, option RS-232
Motor cable length for inverter 7.5 kW to 90 kW Without output choke max. 50 m (shielded)
max. 100 m (unshielded)
With output choke See variant dependent options
for inverter 110 kW to 250 kW Without output choke max. 200 m (shielded)
max. 300 m (unshielded)
With output choke See variant dependent options
Electromagnetic compatibility

 

 

 

for inverter 7.5 kW to 90 kW Inverter with internal filter Class A available
for inverter without filter 7.5 kW to 15 kW EMC filter Class B to EN 55 011 available as an option
18.5 kW to 90 kW EMC filter Class B from Schaffner available as an option
110 kW to 250 kW EMC filter Class A available as an option
Braking DC braking, compound braking
Degree of protection IP20
Operating temperature range

 

for inverter 7.5 kW to 90 kW -10 °C to +40 °C (+14 °F to +104 °F)
for inverter 110 kW to 250 kW 0 °C to +40 °C (+32 °F to +104 °F)
Storage temperature -40 °C to +70 °C (-40 °F to +158 °F)
Relative humidity 95 % (non-condensing)
Installation altitude

 

for inverter 7.5 kW to 90 kW up to 1000 m above sea level without derating
for inverter 110 kW to 250 kW up to 2000 m above sea level without derating
Standard SCCR
(Short Circuit Current Rating) 2)
FSC: 100 kA
FSD, FSE, FSF, FSFX, FSGX: 65 kA
Protection features for undervoltage, overvoltage, overload, earth faults, short-circuits, stall prevention, locked motor protection, motor overtemperature, inverter overtemperature, parameter change protection
Conformity with standards for inverter 7.5 kW to 90 kW  UL, cUL, CE, c-tick
for inverter 110 kW to 250 kW UL available soon, cUL available soon, CE
CE marking Conformity with low-voltage directive 73/23/EEC
Cooling-air volumetric flow required, dimensions and weights (without options)

 

Frame size (FS) Cooling-air volumetric flow required (l/s)/(CFM) H x W x D (mm) Weight, approx. (kg)
C 54.9/116.3 245 x 185 x 195 5.7
D 2 x 54.9/2 x 116.3 520 x 275 x 245 17
E 2 x 54.9/2 x 116.3 650 x 275 x 245 22
F without filter 150/317.79 850 x 350 x 320 56
F with filter 150/317.79 1150 x 350 x 320 75
FX 225/478.13 1400 x 326 x 356 116
GX 440/935 1533 x 326 x 545 174
CFM:
Cubic Feet per Minute
 

 

Do you like this item?