MICROMASTER 440 Inverter 7.5KW With Bilt-in Class a Filter3AC 380-480V 6SE6440-2AD27-5CA1

6SE6440-2AD27-5CA1 MICROMASTER 440 WITH BUILT-IN CLASS A FILTER 3AC 380-480 V +10/-10% 47-63 HZ CONSTANT TORQUE POWER 7.5 KW OVERLOAD 150% 60 S

Sharing good things

Description

MICROMASTER 440 WITH BUILT-IN CLASS A FILTER 3AC 380-480 V +10/-10% 47-63 HZ CONSTANT TORQUE POWER 7.5 KW OVERLOAD 150% 60 S, 200% 3 S SQUARED TORQUE POWER 11 KW 245 X 185 X 195 (H X W X D) PROTECTION IP20 AMBIENT TEMP. -10 TO +50 DEG. C WITHOUT AOP/BOP 6SE6440-2AD27-5CA1_datasheet_en

Technical specifications

Technical dataMICROMASTER 440
Mains voltage and power rangesCT (constant torque)VT (variable torque)
200 V to 240 V 1 AC  ±10 %0.12 kW to 3 kW
200 V to 240 V 3 AC  ±10 %0.12 kW to 45 kW5.5 kW to 55 kW
380 V to 480 V 3 AC  ±10 %0.37 kW to 200 kW7.5 kW to 250 kW
500 V to 600 V 3 AC  ±10 %0.75 kW to 75 kW1.5 kW to 90 kW
Input frequency47 Hz to 63 Hz
Output frequencyin V/f mode

 

for inverter 0.12 kW to 75 kW0 … 650 Hz, (limitation to 550 Hz in production to comply with legal requirements) 1)
for inverter 90 kW to 200 kW0 Hz to 267 Hz
in vector mode

 

for inverter 0.12 kW to 75 kW0 Hz to 200 Hz
for inverter 90 kW to 200 kW0 Hz to 200 Hz
Power factor≥ 0.95
Inverter efficiency0.12 kW to 75 kW: 96 % to 97 %; 90 kW to 200 kW: 97 % to 98 %
Overload capability

CT mode

for inverter 0.12 kW to 75 kWOverload current 1.5 x rated output current (i.e. 150 % overload capability) for 60 s, cycle time 300 s, and 2 x rated output current (i.e. 200 % overload capability) for 3 s, cycle time 300 s
for inverter 90 kW to 200 kWOverload current 1.36 x rated output current (i.e. 136 % overload capability) for 57 s, cycle time 300 s, and 1.6 x rated output current (i.e. 160 % overload capability) for 3 s, cycle time 300 s
Overload capability

VT mode

for inverter 5.5 kW to 90 kWOverload current 1.4 x rated output current (i.e. 140 % overload capability) for 3 s, and 1.1 x rated output current (i.e. 110 % overload capability) for 60 s, cycle time 300 s
for inverter 110 kW to 250 kWOverload current 1.5 x rated output current (i.e. 150 % overload capability) for 1 s, and 1.1 x rated output current (i.e. 110 % overload capability) for 59 s, cycle time 300 s
Inrush currentnot higher than rated input current
Control methodVector control, torque control, linear V/f characteristic; quadratic V/f characteristic; multipoint characteristic (programmable V/f characteristic); flux current control (FCC)
Pulse frequencyfor inverter 0.12 kW to 75 kW4 kHz (standard); 16 kHz (standard with 230 V inverters 0.12 kW to 5.5 kW)
2 kHz to 16 kHz (in 2 kHz steps)
for inverter 90 kW to 200 kW2 kHz (standard with VT mode); 4 kHz (standard with CT mode)
2 kHz to 4 kHz (in 2 kHz steps)
Fixed frequencies15, programmable
Skip frequency ranges4, programmable
Setpoint resolution0.01 Hz digital
0.01 Hz serial
10 bit analog
Digital inputs6 fully programmable isolated digital inputs; switchable PNP/NPN
Analog inputs2 programmable analog inputs

  • 0 V to 10 V, 0 mA to 20 mA and -10 V to +10 V (AIN1)
  • 0 V to 10 V and 0 mA to 20 mA (AIN2)
  • both can be used as 7th/8th digital input
Relay outputs3, programmable
30 V DC/5 A (resistive load)
250 V AC/2A (inductive load)
Analog outputs2, programmable (0/4 mA to 20 mA)
Serial interfacesRS-485, optional RS-232
Motor cable lengthsWithout output chokefor inverter 0.12 kW to 75 kWmax. 50 m (shielded)
max. 100 m (unshielded)
for inverter 90 kW to 250 kWmax. 200 m (shielded)
max. 300 m (unshielded)
With output chokesee variant dependent options
Electromagnetic compatibility (see Selection and Ordering Data)EMC filter, Class A or Class B to EN 55 011 available as an option
Inverter with internal filter Class A available
BrakingResistance braking with DC braking, compound braking, integrated brake chopper (integrated brake chopper only with 0.12 kW to 75 kW inverters)
Degree of protectionIP20
Operating temperature (without derating)for inverter 0.12 kW to 75 kWCT: -10 °C to +50 °C (+14 °F to +122 °F)
VT: -10 °C to +40 °C (+14 °F to +104 °F)
for inverter 90 kW to 200 kW0 °C to +40 °C (+32 °F to +104 °F)
Storage temperature-40 °C to +70 °C (-40 °F to +158 °F)
Relative humidity95 % (non-condensing)
Installation altitudefor inverter 0.12 kW to 75 kWup to 1000 m above sea level without derating
for inverter 90 kW to 200 kWup to 2000 m above sea level without derating
Standard SCCR
(Short Circuit Current Rating) 2)
FSA, FSB, FSC: 100 kA
FSD, FSE, FSF, FSFX, FSGX: 65 kA
Protection features forUndervoltage, overvoltage, overload, earth faults, short-circuits, stall prevention, locked motor protection, motor overtemperature, inverter overtemperature, parameter change protection
Compliance with standardsuL, c uL, CE, c-tick
CE markingConformity with low-voltage directive 73/23/EEC
Cooling-air volumetric flow required, dimensions and weights (without options)Frame size (FS)Cooling-air volumetric flow required (l/s)/(CFM)H x W x D, max. (mm)Weight, approx. (kg)
A4.8/10.2173 x 73 x 1491.3
B24/51202 x 149 x 1723.4
C54.9/116.3245 x 185 x 1955.7
D2 x 54.9/2 x 116.3520 x 275 x 24517
E2 x 54.9/2 x 116.3650 x 275 x 24522
F without filter150/317.79850 x 350 x 32056
F with filter150/317.791150 x 350 x 32075
FX225/478.131400 x 326 x 356116
GX440/9351533 x 326 x 545174
CFM:
Cubic Feet per Minute
 

 

Get Quote